ZN63 (VS1) -12 indoor side-mounted high voltage vacuum circuit breaker

ZN63 (VS1) -12 series indoor high-voltage vacuum circuit breaker is an indoor high-voltage switchgear with a rated voltage of 24KV and three-phase AC 50Hz. It is suitable for control and protection switches of power transmission and distribution systems in power plants, substations, industrial and mining enterprises, etc., especially for breaking important loads and frequent operations in high-altitude areas.

The circuit breaker is manufactured in accordance with the national standard G81984-2003 "AC High Voltage Circuit Breaker" DUT403-2000 (3.6~40.5kV Indoor Vacuum Circuit Breaker Ordering Technical Conditions) and related IEC standards and has a reliable interlocking function.

The operating mechanism of the circuit breaker is a spring energy storage type, which can be operated by AC or DC energy storage, or manually.

The circuit breaker can also be equipped with a long-life permanent-contact operating mechanism with a mechanical life of up to 60,000 times, and can be used in situations where operations are extremely frequent.

The circuit breaker is designed as a front and rear assembly structure, which can be used as a fixed installation unit or assembled with a chassis vehicle as a mid-mounted unit.

    Usage Environment

    ◆Ambient temperature: not higher than 40℃, not lower than -10℃ (storage and transportation at -30℃ is allowed).

    ◆Altitude: not more than 3000m. (If the altitude needs to be increased, the rated discharge level will be increased accordingly)

    ◆Relative humidity: daily average value is not more than 95%, daily average value of saturated vapor pressure is not more than 2.2x10-3MPa, and monthly average value is not more than 1.8x10-3MPa.

    ◆Earthquake intensity: no more than 8 levels.

    ◆Places free from fire, explosion, severe pollution, chemical corrosion and severe vibration.

    Technical Parameters

    Serial number

    Name

    Unit

    D

    1

    Rated voltage

    kV

    12

    2

    Maximum operating voltage

    kV

    12

    3

    Rated current

    A

    630 1250                     

        630 1250       1600 2000   2500 3150

    1250 1600   2000 2500  3150 4000

    4

    Rated short-circuit breaking current (Rated thermal stability current - effective value )

    kA

    20/25

    31.5

    40

    5

    Rated short-circuit making current (peak value)

    kA

    50/63

    80

    100

    6

    Rated peak withstand current  (rated dynamic stability current - peak value)

    kA

    50/63

    80

    100

    7

    4S Rated short circuit withstand current

    kA

    20/25

    31.5

    40

    8

    Rated insulation level

    Working withstand voltage (rated breaking before and after )/1min power frequency withstand voltage

    kV

    To ground 42 (break 48)

    Impulse withstand voltage (rated before and after breaking)/rated lightning impulse withstand voltage peak

    To ground 75 (break 85)

    9

    Rated thermal stabilization time

    s

    4

    10

    Rated operating sequence

     

    split-0.3S-close split-1805-close split

    11

    Mechanical life

    Second-rate

    20000

    12

    Rated short-circuit breaking current breaking times

    Second-rate

    50

    13

    Rated closing voltage of operating mechanism (DC)

    V

    AC、DC 110,220

    14

    Rated trip voltage of operating mechanism (DC)

    V

    AC、DC 110,220

    15

    Contact opening distance

    mm

    11±1

    16

    Overtravel (contact spring compression length)

    mm

    3.5±0.5

    17

    Three-phase opening and closing bounce time

    ms

    ≤2

    18

    Contact closing bounce time

    ms

    ≤2

    19

    Average opening speed

    m/s

    0.9-1.2

    Average closing speed

    m/s

    0.5-0.8

    20

    Opening time

    Maximum operating voltage

    s

    ≤0.05

    21

    Minimum operating voltage

    ≤0.08

    22

    Closing time

    s

    0.1

    23

    Main circuit resistance of each phase

    νΩ

    630≤50 1250≤45

    24

    Allowable wear accumulation thickness of moving and static contacts

    mm

    3