Leave Your Message

ZN85-40.5 Indoor high voltage vacuum circuit breaker

ZN85-40.5 series indoor high-voltage vacuum circuit breaker (hereinafter referred to as circuit breaker) is suitable for three-phase AC 50Hz, rated voltage 40.5kv power system, and can be used for industrial and mining enterprises, power plants and substations to separate and connect load current, overload current and fault current. The circuit breaker and the operating mechanism adopt an upper and lower arrangement structure, which effectively reduces the depth of the circuit breaker. The overall layout is reasonable, beautiful and simple. It is small in size, flexible in operation, has reliable electrical performance, long service life, easy maintenance, and maintenance-free mechanism.

This circuit breaker is suitable for frequent operations, various occasions and places with harsh operating conditions.

    Overview

    The three-phase arc extinguishing chamber and the phase-connected live body are isolated by three independent epoxy resin green insulation cylinders to form a composite insulation structure. The circuit breaker meets the air distance and creepage distance requirements under normal operating conditions and effectively reduces the volume of the circuit breaker. The vacuum arc extinguishing chamber of the main conductive circuit and the dynamic and static conductive connection are installed in the insulation cylinder, so that the phase spacing is only 300mm. The main circuit electrical connection is all fixed, which has high reliability. The insulation cylinder is installed above the circuit breaker frame.

    The spring lifting mechanism designed for this circuit breaker is installed in the circuit breaker frame. Its structural characteristics are more suitable for the upper and lower arrangement of the circuit breaker and become an inseparable part of the overall structure of the circuit breaker. The mechanism design is simple, and the output curve and its performance are suitable for the characteristics and requirements of 40.5kV vacuum circuit breakers.

    Technical Parameters

    Name

    Unit

    Data

    Rated voltage

    kV

    40.5

    1min power frequency withstand voltage (effective value)

    kV

    95

    Lightning impulse withstand voltage (peak value)

    kV

    185

    Rated frequency

    Hz

    50

    Rated current

    A

    125,016,002,000

    Rated short-time withstand current

    kA

    25,31.5

    Rated peak withstand current

    kA

    63,80

    Rated short circuit duration

    s

    4

    Rated short-circuit breaking current

    kA

    25,31.5

    Rated short-circuit making current

    kA

    63,80

    Rated operating sequence

     

    O-0.3s-CO-180s-CO

    Breaking time

    ms

    <80

    Rated short-circuit breaking current breaking times

    Second-rate

    20

    Single capacitor bank breaking current

    A

    630

    Back-to-back capacitor bank breaking current

    A

    400

    Rated operating voltage

    V

    AC110,220: DC110,220

    Mechanical life

    Second-rate

    10000