YBG-35/0.315 Photovoltaic European Transformer
Product Overview
In order to enhance the durability of the box, the base and all exposed metal parts have been treated with anti-corrosion and anti-rust, and sprayed with a durable protective layer to ensure long-term use in various environmental conditions. The top cover of the box is designed with a rainproof sealing cover and rainproof eaves. The double-layer structure of the top cover effectively prevents heat radiation, further improving the safety and stability of the equipment.
Considering the special environmental conditions in the area where the photovoltaic power station is located, such as low temperature, large temperature difference, high humidity and strong wind and sand, the box-type transformer has a reasonable protective structure and dustproof design to ensure its normal and safe operation in harsh environments. Its low temperature resistance and protective measures enable the box-type transformer to work stably under various extreme climatic conditions and meet the high standards of users.
The box-type transformer consists of three main parts: the high-voltage room, the low-voltage room and the transformer. The structural design is flexible and can be arranged in a "目" shape or a "品" shape according to actual needs. This modular design not only optimizes space utilization, but also facilitates maintenance and operation. The inner and outer surfaces of the box are finely processed to ensure that they are flat and smooth, without rust, coating shedding or bump damage. The coating layer is evenly and firmly applied, avoiding obvious contrast and reflection, and improving the overall aesthetics and durability.
Environmental conditions for use
◆Altitude is generally not more than 4000m;
◆Ambient temperature range: -40℃-+85℃;
◆Outdoor wind speed does not exceed 35m/s;
◆Shockproof: horizontal acceleration 0.3m/s2; vertical acceleration no more than 0.15m/s2:
◆Fouling prevention level: Level III:
◆Installation location: Outdoor:
◆When the above normal use environment conditions are exceeded, our company can provide personalized design according to user requirements.
Main technical parameters
Conventional transformer technical parameters
|
Transformer |
High voltage combination and tapping range |
Link group |
No-load |
Load loss |
Impedance% |
||
|
High voltage kV |
Tap range % |
Low voltage kV |
|||||
|
500~1600 |
6、12、24、35、 |
±2x2.5 |
0.315、0.27、 |
Yd11,d11 |
According to |
According to |
6.5 |
Technical parameters of high voltage vacuum isolating load switch and fuse combination electrical appliances
|
Project |
Parameter |
|
|
Model |
FZRN25-12D |
FZRN21C-40.5D |
|
Voltage level(kV) |
12 |
40.5 |
|
Power frequency withstand voltage(kV) |
45 |
95 |
|
Lightning impulse voltage(kV) |
75 |
185 |
|
Rated current(A) |
Based on the fuse |
Based on the fuse |
|
Rated short-time breaking current (kA) |
20/31.5 |
20/31.5 |
|
Mechanical life |
10000 times |
10000 times |
High voltage oil immersed fuse technical parameters
|
Project |
Parameter |
|
|
Model |
XRNT-12 |
XRNT-40.5 |
|
Fuse rated current (A) |
125 |
40 |
|
Rated current of fuse(A) |
50(500kVA630kVA) |
16(500kVA,630kVA) |
|
Fuse short-circuit breaking current (kA) |
31.5 |
31.5 |
|
After the fuse is blown, it can be easily replaced on site. |
||
High voltage arrester technical parameters
|
Project |
Parameter |
|
|
Model |
YH5WZ-17/45 |
YH5WZ-51/134 |
|
Type |
Gapless Metal Zinc Oxide Arrester |
Gapless Metal Zinc Oxide Arrester |
|
Rated voltage (kV) |
17 |
51 |
|
Continuous operating voltage(A) |
13.5 |
40.8 |
|
DC 1mA reference voltage (kV) |
≥24 |
≥73 |
|
Nominal discharge current (kV(peak) |
≥10 |
≥5 |
|
Nominal discharge current Current residual voltage (kV (peak) |
≤45 |
≤134 |
|
2ms square wave current tolerance (A) (peak value) |
150 |
600~800 |
Technical parameters of low voltage frame circuit breaker
|
Project |
Parameter |
|
Rated voltage M |
400 |
|
Rated current(A) |
1250, 1600, 2000, 2500, 3200 |
|
Short-time withstand current and time (kA/1s) |
50 |
Lighting maintenance transformer
|
Model |
Rated capacity |
Voltage combination |
Link group label |
Phase |
Frequency |
|
|
Original Edge |
Secondary side |
|||||
|
SG10-D/0.315/0.4 |
According to customer requirements |
0.315kV |
0.4kV |
Dyn11 |
Three-phase |
50Hz |