FZW28-12F Outdoor high voltage vacuum load switch

FZW28-12F series outdoor boundary vacuum load switch is suitable for outdoor three-phase AC power distribution system with rated voltage of 12kV and rated frequency of 50Hz, and is used for opening and closing load current and closing short-circuit current.

FZW28-12F series outdoor boundary vacuum load switch is suitable for substations, industrial and mining enterprises, urban and rural power grids for protection and control and urban and rural power grid automation distribution network and places with frequent operations. FZW28-12F series outdoor boundary vacuum load switch is used as an operating control switch for overhead line distribution system, and there are many types. It has outstanding advantages such as oil-free, simple structure, reliable performance and no maintenance, and has been widely used so far. This product is combined with FDR type fault detector or RTU remote control terminal device and other equipment to form a very simple distribution automation system, which can realize the automatic location of overhead line faults and automatic isolation of fault sections. In order to update the existing distribution switch equipment in my country, it is necessary to realize the transformation of distribution equipment characterized by oil-free and automation.

    Model and meaning

    Model and meaning.jpg

    Features

    Automatic interphase short circuit fault blocking: When the same short circuit fault occurs in the user's branch line, the boundary switch will immediately open and block the substation reclosing after the substation circuit breaker or recloser protection trips, and other branch users on the feeder will quickly resume power supply;

    Quickly locate the fault point: After the boundary switch protection is activated due to a branch line accident, the responsible user will be cut off from power and will take the initiative to report the accident information. The power company's personnel can use a handheld computer or communication module to investigate the cause of the accident on site;

    Automatically cut off single-phase grounding fault: When a single-phase grounding fault occurs in the user's branch line, the boundary switch automatically opens; other branch users on the substation and feeder line cannot feel the occurrence of the fault. This switch can realize the following functions: quick-break protection, overcurrent protection, three-time reclosing, event recording, anti-surge protection, zero-sequence protection, real-time clock acceleration after reclosing, real-time status query, intelligent handheld computer control, local/remote setting of fixed values, active fault reporting, and GSM short message function.

    Technical Parameters

    Name

    Unit

    Numeric

    Rated voltage

    kV

    12

    Rated frequency

    Hz

    50

    Rated insulation level

    Lightning impulse withstand voltage

    kV

    75/85(Brea)

    1 min

    Dry Test

    kV

    42/48(Break)

    Power frequency withstand voltage

    Wet test

    kV

    34

    Rated current

    A

    630

    Rated short-time withstand current and duration

    kA/2s

    16

    Rated peak withstand current

    kA

    40

    Rated short-circuit making current

    kA

    40

    Mechanical life

    Second-rate

    10000

    Net weight

    kg

    210